rootfasad.blogg.se

Ashrae 90.1 2016 table 5.5
Ashrae 90.1 2016 table 5.5







ashrae 90.1 2016 table 5.5

  • Table 6.8.1-6 Gas- and Oil-Fired Boilers-Minimum Efficiency Requirements.
  • Table 6.8.1-5 Warm-Air Furnaces and Combination Warm-Air Furnaces/Air-Conditioning Units,Warm-Air Duct Furnaces, and Unit Heaters-Minimum Efficiency Requirements.
  • Table 6.8.1-4 Electrically Operated Packaged Terminal Air Conditioners, Packaged Terminal Heat Pumps, Single-PackageVertical Air Conditioners, Single-Package Vertical Heat Pumps, Room Air Conditioners, and Room Air-Conditioner HeatPumps-Minimum Efficiency Requirements.
  • Table 6.8.1-3 Water-Chilling Packages-Minimum Efficiency Requirementsa,b,e.
  • Table 6.8.1-2 Electrically Operated Air-Cooled Unitary Heat Pumps-Minimum Efficiency Requirements (Continued).
  • Table 6.8.1-2 Electrically Operated Air-Cooled Unitary Heat Pumps-Minimum Efficiency Requirements.
  • Table 6.8.1-1 Electrically Operated Unitary Air Conditioners and Condensing Units-Minimum Efficiency Requirements (Continued).
  • Table 6.8.1-1 Electrically Operated Unitary Air Conditioners and Condensing Units-Minimum Efficiency Requirements.
  • 6.8.1 Minimum Efficiency Requirement Listed Equipment-Standard Rating and Operating Conditions.
  • 6.8 Minimum Equipment Efficiency Tables.
  • Table 6.5.7.2.2 Maximum Net Exhaust Flow Rate, cfm per Linear Foot of Hood Length.
  • Table 6.5.6.1.2-2 Exhaust Air Energy Recovery Requirementsfor Ventilation Systems Operating Greater than or Equal to 8000 Hours per Year.
  • Table 6.5.6.1.2-1 Exhaust Air Energy Recovery Requirementsfor Ventilation Systems Operating Less than 8000 Hours per Year.
  • Table 6.5.4.2 Pump Flow Control Requirements.
  • 6.5.4 Hydronic System Design and Control.
  • Table 6.5.3.1-2 Fan Power Limitation Pressure Drop Adjustment.
  • 6.5.2 Simultaneous Heating and Cooling Limitation.
  • Table 6.5.1.3 DX Cooling Stage Requirements for Modulating Airflow Units.
  • Table 6.5.1.2.1 Fluid Economizer Sizing Dry-Bulb and Wet-Bulb Requirements for Computer Rooms.
  • Table 6.5.1.1.3 High-Limit Shutoff Control Settings for Air Economizersb.
  • Table 6.5.1-1 Minimum Fan-Cooling Unit Size for which an Economizer Is Required.
  • 6.4.5 Walk-In Coolers and Walk-In Freezers.
  • 6.4.4 HVAC System Construction and Insulation.
  • Table 6.4.3.10.1 DDC Applications and Qualifications.
  • Table 6.4.3.4.3 Maximum Damper Leakagea,b, cfm per ft2 at 1.0 in.
  • 6.4.1 Equipment Efficiencies, Verification, and Labeling Requirements.
  • ashrae 90.1 2016 table 5.5

  • 6.3 Simplified Approach Building Compliance Path for HVAC Systems.
  • 6.2.2 Additional Requirements to Comply with Section 6.
  • 6.2.1 Requirements for all Compliance Paths.
  • 6 Heating, Ventilating, and Air Conditioning.
  • 5.9 Verification, Testing, Commissioning, and Inspection.
  • Table 5.8.3.2 Maximum Air Leakage for Fenestration and Doors.
  • Table 5.8.3.1 Maximum Air Leakage for Materials and Assemblies.
  • 5.8 Product Information and Installation Requirements.
  • 5.6 Building Envelope Trade-Off Compliance Path.
  • Table 5.5.4.4.1 SHGC Multipliers for Permanent Projections.
  • Figure 5.5.2 Exterior and semiexterior building envelope.
  • Table 5.5.3.1.1 Increased Roof Insulation Levels.
  • Table 5.5-8 Building Envelope Requirements for Climate Zone 8*.
  • Table 5.5-7 Building Envelope Requirements for Climate Zone 7*.
  • Table 5.5-6 Building Envelope Requirements for Climate Zone 6 (A,B)*.
  • Table 5.5-5 Building Envelope Requirements for Climate Zone 5 (A,B,C)*.
  • Table 5.5-4 Building Envelope Requirements for Climate Zone 4 (A,B,C)*.
  • Table 5.5-3 Building Envelope Requirements for Climate Zone 3 (A,B,C)*.
  • ashrae 90.1 2016 table 5.5

  • Table 5.5-2 Building Envelope Requirements for Climate Zone 2 (A,B)*.
  • Table 5.5-1 Building Envelope Requirements for Climate Zone 1 (A,B)*.
  • Table 5.5-0 Building Envelope Requirements for Climate Zone 0 (A,B)*.
  • 5.5 Prescriptive Building Envelope Compliance Path.
  • 5.3 Simplified Building Compliance Path.
  • 5.2.2 Additional Requirements to Comply with Section 5.
  • 5.2.1 Requirements for All Compliance Paths.
  • 4.2.5 Verification, Testing, and Commissioning.
  • ashrae 90.1 2016 table 5.5

  • 4.1.9 Reference Standard Reproduction Annexes.
  • 4.1.3 Alternative Materials, Methods of Construction, or Design.
  • 3 Definitions, Abbreviations, and Acronyms.








  • Ashrae 90.1 2016 table 5.5